Chapter 4 Wire GuardPLC 1600, GuardPLC 1800, and GuardPLC 1200 Controllers
GuardPLC 1200 Controller
Both L+ and L- terminals must be used in parallel to allow the
maximum current of 8 A. (Each terminal maximum is 4 A so both are
required for 8 A.)
If the power supply has only one (+) lead, a short bridge jumper must
be installed between L+
(1)
and L+
(2)
.
Safety-related Digital
Inputs
The status of digital inputs is indicated via status indicators when the
controller or module is in Run mode.
Follow the closed-circuit principle for external wiring when
connecting sensors. To create a safe state in the event of a fault, the
input signals revert to the de-energized state (0). The external line is
not monitored, but a wire break is interpreted as a safe (0) signal.
The GuardPLC 1600 and GuardPLC 1800 controllers provide power to
input devices through their LS+ terminals. However, input devices
with their own dedicated power supply can also be connected instead
of contacts. The reference pole (L-) of the power supply must then be
connected to the reference pole (L-) of the appropriate GuardPLC
input group. See the wiring diagrams in
In general, the LS+ terminals, not L+ on the power supply connection,
should be used to supply voltage for safety inputs. Each LS+ features
individual short-circuit and EMC protection. Due to current limitations,
use LS+ for only the safety inputs on the same terminal plug.
An EN 61000-4.5 surge impulse can be read as a short-duration HI
signal in some modules. To avoid an error, either:
•
install shielded input lines to prevent effects of surges in the
system.
•
implement software filtering in the user program. A signal must
be present for at least two cycles before it is evaluated.
TIP
The GuardPLC 1200 controller requires approximately 0.5 A to
operate. The remaining 7.5 A is used to source power for inputs
and outputs.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems