Controller configuration – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 117

Publication 1753-UM001C-EN-P - March 2010
117
Controller Configuration and Modes of Operation Chapter 13
If a routine has already been loaded in the controller when
Failure_Stop occurs, the controller goes to Stop/Valid_Configuration
after booting. If Autostart Enable is activated, the routine starts up
automatically.
If a routine has not been loaded in the controller when Failure_Stop
occurs, the controller goes to Stop/Invalid_Configuration after
booting.
Controller Configuration
To enable the controller to perform its tasks, you have to configure
the controller. The parameters you specify are stored in the
nonvolatile RAM and in the flash file system of the communication
section of the controller.
To configure a controller, follow these steps.
1. In the Hardware Management Window, expand the
Configuration module.
2. Right-click Resource and choose Properties.
3. From the Type pull-down menu, choose your controller.
TIP
If the GuardPLC controller is in Stop/Invalid_Configuration after
booting, you need to update the SRS. From the Extra menu,
choose Change System ID (SRS). Enter the SRS and click OK.
TIP
A brand-new GuardPLC 1200 or 2000 controller, into which a
back-up battery has not yet been installed, is always in
Failure_Stop and must be restarted before you can download a
routine.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems