Use GuardPLC Controller as an Adapter Chapter 19

4. Configure the message parameters as follows.

a. Set Service Type to Get Attribute Single.

b. Set Class to 4 (assembly)

c. Set Instance to 120. This is the assembly instance number that

will be read from.

d. Set Attribute to 3 (assembly data).

e. Set Destination to ReadBuffer.

5. Switch to the Communication tab and enter this text in the Path

field: ENBT,2,.

Here, 2 is the EtherNet/IP port of the 1756-ENBT module.