Use GuardPLC Controller as an Adapter Chapter 19
4. Configure the message parameters as follows.
a. Set Service Type to Get Attribute Single.
b. Set Class to 4 (assembly)
c. Set Instance to 120. This is the assembly instance number that
will be read from.
d. Set Attribute to 3 (assembly data).
e. Set Destination to ReadBuffer.
5. Switch to the Communication tab and enter this text in the Path
field: ENBT,2,
Here, 2 is the EtherNet/IP port of the 1756-ENBT module.
This manual is related to the following products:
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems