The Trend Parameter Definition allows you to read the list of trend
parameter numbers from the database.

PLC Block Transfer Instruction Data

BTW instruction length:

3 words

BTR instruction length:

13 words

Header

Word 1

Header

Word 1

Header

Word 2

Header

Word 2

Header

Word 3

Trend Number

Message Structure

Header

Word 3

Trend Number

PLC Decimal Value

4102

PLC Decimal Value

4102 –– Message OK

–28666 –– Message Error

Message Length

3

Message Length

13

PLC Request –– Block Transfer Write

Drive Response –– Block Transfer Read

Data

Word 4

Data

Word 5

Data

Word 6

Post Samples

Trend Sample Size

Trend Status

Parameter Number

Parameter Number

Parameter Number

Data

Word 7

Data

Word 8

Data

Word 9

Mode

Sample Time Rate

Operator Data

Parameter Number

Parameter Number

Parameter Number

Data

Word 10

Data

Word 11

Data

Word 12

Sampling Input

Comparison B

Comparison A

Parameter Number

Parameter Number

Parameter Number

Data

Word 13

Trend Output

Parameter Number

Message Operation

You can use the Trend Parameter Definition function to read the list
of trend parameter numbers from the database. You can set up trends
using the Trend Setup Data File message or by direct access through
the parameter mechanism.

Trend File

Trend Parameter Definition