Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual
Page 113
![background image](/manuals/578856/113/background.png)
6–23
Publication 1336 FORCE–5.13 –– September, 1998
353
Channel A Remote I/O Output 2
[ChA RIOA Out 2]
–– adapter mode
[ChA/B RIOA Out2]
–– adapter mode with redundancy
[ChA RIOS Out 2]
–– scanner mode
ChA RIOx Out 2 contains the third word or data
group to the PLC controller input image table. The
data is transferred to the PLC controller every rack
scan. The PLC Communications Adapter Board can
provide this value directly. Other drive functions can
provide this value through a configuration link.
Parameter Number
353➀
Parameter Type
Read/Write, Sink
Display Units / Drive Units
None
Factory Default
None
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communications I/O – Channel A
➀ This parameter is not available if you set up channel A for DH+. Availability also
depends on the selected rack size.
Note: All eight words are displayed regardless of the rack size. Only the number of words corresponding to the rack size and protocol
(with or without block transfer) are functional.
354
Channel A Remote I/O Output 3
[ChA RIOA Out 3]
–– adapter mode
[ChA/B RIOA Out3]
–– adapter mode with redundancy
[ChA RIOS Out 3]
–– scanner mode
ChA RIOx Out 3 contains the fourth word or data
group to the PLC controller input image table. The
data is transferred to the PLC controller every rack
scan. The PLC Communications Adapter Board can
provide this value directly. Other drive functions can
provide this value through a configuration link.
Parameter Number
354➀
Parameter Type
Read/Write, Sink
Display Units / Drive Units
None
Factory Default
None
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communications I/O – Channel A
➀ This parameter is not available if you set up channel A for DH+. Availability also
depends on the selected rack size.
Note: All eight words are displayed regardless of the rack size. Only the number of words corresponding to the rack size and protocol
(with or without block transfer) are functional.
355
Channel A Remote I/O Output 4
[ChA RIOA Out 4]
–– adapter mode
[ChA/B RIOA Out4]
–– adapter mode with redundancy
[ChA RIOS Out 4]
–– scanner mode
ChA RIOx Out 4 contains the fifth word or data
group to the PLC controller input image table. The
data is transferred to the PLC controller every rack
scan. The PLC Communications Adapter Board can
provide this value directly. Other drive functions can
provide this value through a configuration link.
Parameter Number
355➀
Parameter Type
Read/Write, Sink
Display Units / Drive Units
None
Factory Default
None
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communications I/O – Channel A
➀ This parameter is not available if you set up channel A for DH+. Availability also
depends on the selected rack size.
Note: All eight words are displayed regardless of the rack size. Only the number of words corresponding to the rack size and protocol
(with or without block transfer) are functional.