Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual
Page 123
6–33
Publication 1336 FORCE–5.13 –– September, 1998
399
Analog Input 4 Scale
[Analog In 4 Scale]
Analog In 4 Scale determines the scale factor or
gain for the Analog In 4 value. A +10V dc signal
applied to Analog In 4 at TB21 is converted to a
+2048 digital value used by the 1336 FORCE.
Before the digital value is displayed or transferred to
the drive, the scale factor is applied allowing an
effective digital range of
±
32767 (16 x 2048). The
absolute digital value is clamped at 32767.
Scale Factor
Drive Units
1
2048
2
4096
4
8192
16
32767
Parameter Number
399
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
±
32767
Factory Default
+1
Minimum Value
–16
Maximum Value
+16
File – Group
Communications I/O – Analog Input
400
Analog Output 1 Offset
[Analog Out 1 Offset]
Analog Out 1 Offset determines the offset applied to
the Analog Out 1 value after the scale factor is
applied. This allows you to shift the range of the
analog output.
Parameter Number
400
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
±
4096
Factory Default
0
Minimum Value
–20 Volts
Maximum Value
+20 Volts
File – Group
Communications I/O – Analog Output
401
Analog Output 1 Scale
[Analog Out 1 Scale]
Analog Out 1 Scale determines the scale factor or
gain for the Analog In 1 value. A +2048 value
corresponds to a +10V output signal at TB21. The
value sent (linked) to Analog Out 1 is scaled by the
corresponding scale parameter before it is offset and
converted to an analog signal.
Scale Factor
Drive Units
1
32767
1/2
16383
1/4
8192
1/16
2048
Parameter Number
401
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
±
32767
Factory Default
+1
Minimum Value
–1
Maximum Value
+1
File – Group
Communication I/O – Analog Output
402
Analog Output 2 Offset
[Analog Out 2 Offset]
Analog Out 2 Offset determines the offset applied to
the Analog Out 2 value after the scale factor is
applied. This allows you to shift the range of the
analog output.
Parameter Number
402
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
±
4096
Factory Default
0
Minimum Value
–20 Volts
Maximum Value
+20 Volts
File – Group
Communications I/O – Analog Output