Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual
Page 124
6–34
Publication 1336 FORCE–5.13 –– September, 1998
403
Analog Output 2 Scale
[Analog Out 2 Scale]
Analog Out 2 Scale determines the scale factor or
gain for the Analog In 2 value. A +2048 value
corresponds to a +10V output signal at TB21. The
value sent (linked) to Analog Out 2 is scaled by the
corresponding scale parameter before it is offset and
converted to an analog signal.
Scale Factor
Drive Units
1
32767
1/2
16383
1/4
8192
1/16
2048
Parameter Number
403
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
±
32767
Factory Default
+1
Minimum Value
–1
Maximum Value
+1
File – Group
Communication I/O – Analog Output
404
Analog Output 3 Offset
[Analog Out 3 Offset]
Analog Out 3 Offset determines the offset applied to
the Analog Out 3 value after the scale factor is
applied. This allows you to shift the range of the
analog output.
Parameter Number
404
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
±
4096
Factory Default
0
Minimum Value
–20 Volts
Maximum Value
+20 Volts
File – Group
Communications I/O – Analog Output
405
Analog Output 3 Scale
[Analog Out 3 Scale]
Analog Out 3 Scale determines the scale factor or
gain for the Analog In 3 value. A +2048 value
corresponds to a +10V output signal at TB21. The
value sent (linked) to Analog Out 3 is scaled by the
corresponding scale parameter before it is offset and
converted to an analog signal.
Scale Factor
Drive Units
1
32767
1/2
16383
1/4
8192
1/16
2048
Parameter Number
405
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
±
32767
Factory Default
+1
Minimum Value
–1
Maximum Value
+1
File – Group
Communication I/O – Analog Output
406
Analog Output 4 Offset
[Analog Out 4 Offset]
Analog Out 4 Offset determines the offset applied to
the Analog Out 4 value after the scale factor is
applied. This allows you to shift the range of the
analog output.
Parameter Number
406
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
±
4096
Factory Default
0
Minimum Value
–20 Volts
Maximum Value
+20 Volts
File – Group
Communications I/O – Analog Output