Channel B LED State
[ChB LED State]
ChB LED State displays the current LED state for
channel B. The LED states correspond to LEDs
D13, D14, and D15 on the PLC Communications
Adapter Board.
Parameter Number
306
Parameter Type
Read Only, Source
Display Units / Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
5
File – Group
Diagnostics – Info
Enums
0 = Off
1 = Red
2 = Green
3 = Yellow
4 = Flash Green
5 = Flash Red
307
PLC Communications Board Status
[PLC Comm Status]
PLC Comm Status displays the status of the PLC
Communications Adapter Board. You can use this
parameter to determine if no fault occurred, or if a
warning, soft fault, or hard fault occurred.
Parameter Number
307
Parameter Type
Read Only, Source
Display Units / Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
3
File – Group
Diagnostics – Info
Enums
0 = No Faults
1 = Drv Warning
2 = Drv Soft Flt
3 = Drv Hard Flt
309
Language Select
[Language Sel]
You can use Language Sel to choose the language
you want the PLC Communications Adapter Board
to use for parameter and fault display text.
Currently, only English is available.
Parameter Number
309
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
1
File – Group
Startup – Drive Data Group
Diagnostics – Info
Enums
0 = English
1 = Alternate Language (not currently available)
314
Data Input A1
[Data In A1]
Data In A1 contains the first image word from the
SCANport output image table.
Parameter Number
314
Parameter Type
Read Only, Source
Display Units / Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communications I/O – SCANport I/O
315
Data Input A2
[Data In A2]
Data In A2 contains the second image word from the
SCANport output image table.
Parameter Number
315
Parameter Type
Read Only, Source
Display Units / Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communications I/O – SCANport I/O
316
Data Input B1
[Data In B1]
Data In B1 contains the third image word from the
SCANport output image table.
Parameter Number
316
Parameter Type
Read Only, Source
Display Units / Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communications I/O – SCANport I/O