Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual
Page 120
6–30
Publication 1336 FORCE–5.13 –– September, 1998
386
SCANport Analog Output
[SP Analog Out]
SP Analog Out passes the value it contains to the
attached SCANport devices. For example, you can
link one of the output parameters to SP Analog Out
and each of the five SCANport devices could read
the value of the output parameter.
Parameter Number
386
Parameter Type
Read/Write, Sink
Display Units / Drive Units
±
32767
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communications I/O – Analog Output
387
Analog Output 1
[Analog Out 1]
Analog Out 1 converts a
±
32767 value to a
±
10V
signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where
±
2048 results in a
±
10V
output.
Parameter Number
387
Parameter Type
Read/Write, Sink
Display Units / Drive Units
±
32767
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communication I/O – Analog Output
388
Analog Output 2
[Analog Out 2]
Analog Out 2 converts a
±
32767 value to a
±
10V
signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where
±
2048 results in a
±
10V
output.
Parameter Number
388
Parameter Type
Read/Write, Sink
Display Units / Drive Units
±
32767
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communication I/O – Analog Output
389
Analog Output 3
[Analog Out 3]
Analog Out 3 converts a
±
32767 value to a
±
10V
signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where
±
2048 results in a
±
10V
output.
Parameter Number
389
Parameter Type
Read/Write, Sink
Display Units / Drive Units
±
32767
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communication I/O – Analog Output
390
Analog Output 4
[Analog Out 4]
Analog Out 4 converts a
±
32767 value to a
±
10V
signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where
±
2048 results in a
±
10V
output.
Parameter Number
390
Parameter Type
Read/Write, Sink
Display Units / Drive Units
±
32767
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communication I/O – Analog Output