Channel B Remote I/O Fault Select

[ChB RIOA Flt Sel]

–– adapter mode

[ChB RIOS Flt Sel]

–– scanner mode

ChB RIOx Flt Sel dictates whether the PLC
Communications Adapter Board will report a fault
condition if a PLC controller RIO communications
fault occurs at channel B.

If a bit is zero, parameter 426 is checked to see
whether a warning condition should be reported.

ChB RIOx Flt Sel is not used if channel B is set up
for DH+ communications.

Parameter Number

430

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

Bits

Factory Default

15

Minimum Value

0

Maximum Value

15 (adapter) or 255 (scanner)

File – Group

Diagnostics – Fault Select/Status

Communication I/O – Fault Select/Status

When RIO adapter is used:
Enums

Bits 7–4 Bit 3 Bit 2 Bit 1 Bit 0

Res/Pgm/Test (Flt 36024)
0 = No drive soft fault
1 = Drive soft fault

Comm Loss (Flt 36022)
0 = No drive soft fault
1 = Drive soft fault

Last State
0 = Data zeroed
1 = Last state

Rack Inhibit (Flt 36025)
0 = No drive soft fault
1 = Drive soft fault

Not used

When RIO scanner is used:
Enums

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Rck Flt Grp 0
0 = No rack fault
1 = Rack fault

Rck Flt Grp 2
0 = No rack fault
1 = Rack fault

Rck Flt Grp 4
0 = No rack fault
1 = Rack fault

Rck Flt Grp 6
0 = No rack fault
1 = Rack fault

Inhibit Grp 0
0 = Group 0 not inhibited
1 = Inhibit group 0

Inhibit Grp 2
0 = Group 2 not inhibited
1 = Inhibit group 2

Inhibit Grp 4
0 = Group 4 not inhibited
1 = Inhibit group 4

Inhibit Grp 6
0 = Group 6 not inhibited
1 = Inhibit group 6