Channel b remote i/o fault select – Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual
Page 131
6–41
Publication 1336 FORCE–5.13 –– September, 1998
430
Channel B Remote I/O Fault Select
[ChB RIOA Flt Sel]
–– adapter mode
[ChB RIOS Flt Sel]
–– scanner mode
ChB RIOx Flt Sel dictates whether the PLC
Communications Adapter Board will report a fault
condition if a PLC controller RIO communications
fault occurs at channel B.
If a bit is zero, parameter 426 is checked to see
whether a warning condition should be reported.
ChB RIOx Flt Sel is not used if channel B is set up
for DH+ communications.
Parameter Number
430
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
Bits
Factory Default
15
Minimum Value
0
Maximum Value
15 (adapter) or 255 (scanner)
File – Group
Diagnostics – Fault Select/Status
Communication I/O – Fault Select/Status
When RIO adapter is used:
Enums
Bits 7–4 Bit 3 Bit 2 Bit 1 Bit 0
Res/Pgm/Test (Flt 36024)
0 = No drive soft fault
1 = Drive soft fault
Comm Loss (Flt 36022)
0 = No drive soft fault
1 = Drive soft fault
Last State
0 = Data zeroed
1 = Last state
Rack Inhibit (Flt 36025)
0 = No drive soft fault
1 = Drive soft fault
Not used
When RIO scanner is used:
Enums
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Rck Flt Grp 0
0 = No rack fault
1 = Rack fault
Rck Flt Grp 2
0 = No rack fault
1 = Rack fault
Rck Flt Grp 4
0 = No rack fault
1 = Rack fault
Rck Flt Grp 6
0 = No rack fault
1 = Rack fault
Inhibit Grp 0
0 = Group 0 not inhibited
1 = Inhibit group 0
Inhibit Grp 2
0 = Group 2 not inhibited
1 = Inhibit group 2
Inhibit Grp 4
0 = Group 4 not inhibited
1 = Inhibit group 4
Inhibit Grp 6
0 = Group 6 not inhibited
1 = Inhibit group 6