Index indicates the index into the 500 word buffer where the last data
point was written.
Timestamp is updated when the last (500
th
) data point is written.
The time stamp has the following format:
This field:
Indicates:
Ticks
The number of ticks. One tick equals two
milliseconds. Valid values are 0 through 499.
Seconds
The number of seconds. Valid values are 0 through
59.
Minute
The number of minutes passed the hour. Valid
values are 0 through 59.
Hour
The hour. Valid values are 0 through 23.
If you request less than 32 trend samples, then run–time data is
padded with zeros. If you request data samples past the end of the
buffer, then run–time data is padded with zeros.
Important: The data samples that you are reading are not being
read from the trend file. Instead, the data samples are
read from the running trend buffer. This buffer is
continually changing at the rate specified by the
sampling rate for that particular trend. You should use
this function when you want to monitor the current
trend sampling.
Example
In this example, Trend 1 is sampling the Velocity Feedback as it is
hovering around 1750 rpm. The data is displayed in internal drive
units.
1
0
N10:10
2
3
4
5
6
7
8
9
N10:90
BTW
Data File
BTR
Data File
Data Format
4128
4128
4093
3
35
4100
4100
4092
4093
4092
4091
4094
4093
N10:100
4092
4091
4092
4091
4091
4092
4093
4094
4094
4093
N10:110
4093
4094
4092
4091
4092
Run File Data
(continued)