Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual
Page 212
7–66
Publication 1336 FORCE–5.13 –– September, 1998
Message Operation
You can use the All Info function to read the set up information for a
trend file in one message as opposed to the individual parameters
within the drive.
The following are the valid trend numbers:
This
number:
Specifies that the command is to be sent for:
4096
Trend 1
8192
Trend 2
12228
Trend 3
16384
Trend 4
The following are the possible status values:
This
number:
Indicates that the trend is:
1
Stopped.
2
Running.
3
In the tripped trigger state. The condition has
become true, and the post samples are being taken.
4
In the forced trigger state. The trigger condition
was forced to be true so that the post samples
could be taken.
Trend Sample Size is always 500.
Post Samples specifies the number of samples that are taken once the
trigger condition has been tripped or is forced. One sample is used
for the instance when the trigger becomes true.
Operator data specifies how to compare the two data values for the
trigger condition.
Sample Time Rate specifies the rate of sampling data value. An
entry of 1 specifies 2 milliseconds.
Mode specifies whether a continuous trend or a one–shot trend is
performed.
If Comparison A Value is non–zero, the value specifies a constant
value to use as Operand X. You need to specify the Comparison A
Value in internal drive units. If Comparison A Value is zero,
Operand X is specified by Comparison A Link.
All Info
(continued)