Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual
Page 142
6–52
Publication 1336 FORCE–5.13 –– September, 1998
477
Trend 3 Operator
[Tr3 Operator]
Tr3 Operator specifies the operator used for the
trend trigger evaluation. The available operators
are:
Value
Description
1
Greater Than
(.GT.)
2
Less Than
(.LT.)
3
Equals
(.EQ.)
4
Not Equals
(.NE.)
5
Logical AND
(.AND.)
6
Logical NAND (.NAND.)
7
Logical OR
(.OR.)
8
Logical NOR
(.NOR.)
Parameter Number
477
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
None
Factory Default
5
Minimum Value
1
Maximum Value
8
File – Group
Diagnostics – Trend Setup
478
Trend 3 Sample Rate
[Tr3 Sample Rate]
Tr3 Sample Rate specifies the interval at which the
data in the Trend In 3 parameter is sampled. It is
programmable in 2 millisecond increments. All
values are rounded down to the nearest 2
millisecond interval.
Parameter Number
478
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
Seconds
Factory Default
0.020 Seconds
Minimum Value
0.002 Seconds
Maximum Value
30 Seconds
File – Group
Diagnostics – Trend Setup
479
Trend 3 Post Samples
[Tr3 Post Samples]
Tr3 Post Samples specifies the number of data
samples to be gathered once the trigger evaluation
becomes true. There is always a sample reserved
for the instance when the trigger condition becomes
true.
Parameter Number
479
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
None
Factory Default
15
Minimum Value
0
Maximum Value
499
File – Group
Diagnostics – Trend Setup
480
Trend 3 Continuous Trigger
[Tr3 Cont Trigger]
Tr3 Cont Trigger specifies the type of trend. You can
choose either 0 for one–shot or 1 for continuous.
With a one–shot trend, once the trigger condition is
true and the number of samples after the trigger is
taken are gathered, the trend stops.
With a continuous trend, once the trigger condition is
true and the number of samples after the trigger is
taken are gathered, the trend continues looking for
the next occurrence of a true trigger condition.
Parameter Number
480
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
1
File – Group
Diagnostics – Trend Setup