6–29
Publication 1336 FORCE–5.13 –– September, 1998
375
Local Owner
[Local Owner]
Local Owner displays which port has requested
exclusive control of all drive logic functions. If a port
is in local lockout, all other functions (except stop)
on all other ports are locked out and are
non–functional.
Parameter Number
375
Parameter Type
Read Only, Source
Display Units / Drive Units
Bits
Factory Default
0
Minimum Value
0
Maximum Value
0FE Hex
File – Group Communications I/O – SCANport Owners
Enums
Bit 1 = Port 1
Bit 2 = Port 2
Bit 3 = Port 3
Bit 4 = Port 4
Bit 5 = Port 5
Bit 6 = Channel A Bit 7 = Channel B
376
Flux Owner
[Flux Owner]
Flux Owner displays which ports are presently
issuing a valid Flux Enable command.
Parameter Number
376
Parameter Type
Read Only, Source
Display Units / Drive Units
Bits
Factory Default
0
Minimum Value
0
Maximum Value
0FE Hex
File – Group Communications I/O – SCANport Owners
Enums
Bit 1 = Port 1
Bit 2 = Port 2
Bit 3 = Port 3
Bit 4 = Port 4
Bit 5 = Port 5
Bit 6 = Channel A Bit 7 = Channel B
377
Trim Owner
[Trim Owner]
Trim Owner displays which port is presently issuing
a Trim Enable command.
Parameter Number
377
Parameter Type
Read Only, Source
Display Units / Drive Units
Bits
Factory Default
0
Minimum Value
0
Maximum Value
0FE Hex
File – Group Communications I/O – SCANport Owners
Enums
Bit 1 = Port 1
Bit 2 = Port 2
Bit 3 = Port 3
Bit 4 = Port 4
Bit 5 = Port 5
Bit 6 = Channel A Bit 7 = Channel B
378
Ramp Owner
[Ramp Owner]
Ramp Owner displays which port is presently issuing
a Ramp command.
Parameter Number
378
Parameter Type
Read Only, Source
Display Units / Drive Units
Bits
Factory Default
0
Minimum Value
0
Maximum Value
0FE Hex
File – Group Communications I/O – SCANport Owners
Enums
Bit 1 = Port 1
Bit 2 = Port 2
Bit 3 = Port 3
Bit 4 = Port 4
Bit 5 = Port 5
Bit 6 = Channel A Bit 7 = Channel B
379
Clear Fault Owner
[Clr Fault Owner]
Clr Fault Owner displays which port is presently
issuing a Clear Fault command.
Parameter Number
379
Parameter Type
Read Only, Source
Display Units / Drive Units
Bits
Factory Default
0
Minimum Value
0
Maximum Value
0FE Hex
File – Group Communications I/O – SCANport Owners
Enums
Bit 1 = Port 1
Bit 2 = Port 2
Bit 3 = Port 3
Bit 4 = Port 4
Bit 5 = Port 5