Time stamp, Plc block transfer instruction data, Message operation – Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual
Page 199: Reference time stamp data write
7–53
Publication 1336 FORCE–5.13 –– September, 1998
The Reference Time Stamp message is provided to allow the drive to
write the specified real–time clock. This allows the drive to write a
new reference stamp.
PLC Block Transfer Instruction Data
BTW instruction length:
7 words
BTR instruction length:
3 words
Header
Word 1
Header
Word 1
Header
Word 2
Header
Word 2
Header
Word 3
0
Message Structure
Message Length
7
Header
Word 3
0
PLC Decimal Value
-29952
Clock Time
Seconds
10ths of MS
Clock Time
Hour
Minute
PLC Decimal Value
2816 –– Message OK
-29952 –– Message Error
Clock Time
Date
Day
Clock Time
Year
Month
Data
Word 4
Data
Word 5
Data
Word 6
Data
Word 7
0
PLC Request –– Block Transfer Write
Drive Response –– Block Transfer Read
Message Operation
The Reference Time Stamp Data Write allows you to define a
specific time stamp to be used in the drive.
The Time is based on a 24–hour clock.
This field:
Indicates:
Seconds
The seconds and tenths of milliseconds.
Date
The date of the month in ASCII.
Day
The day of the week, where 1 is Sunday and 7 is
Saturday.
Year
The number of the year. 1990 is referenced as 0.
Therefore, the year 1995 would return a value of 5.
Month
The month of the year, where 1 is January and 12 is
December.
Time Stamp
Reference Time Stamp Data
Write