5

Motor control (MCTRL)

5.1

Motor selection/Motor data

72

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Preconditions
The motor parameters listed in the table below are excluded from automatic identification and

must therefore be adapted to the used motor before motor parameter identification is carried out

(see motor nameplate).

Duration & sequence of the motor parameter identification
The duration of the motor parameter identification is approx. 30 s. The following steps are carried

out during this time:

1. The motor stator resistance (

C084

) is measured.

2. The inverter error characteristic is measured.
3. The motor stator leakage inductance (

C085

) is measured

4. The motor magnetising inductance (

C092

) is measured

5. The motor magnetising current (

C095

) is measured.

6. The V/f base frequency (

C015

) is calculated.

7. The slip compensation (

C021

) is calculated.

8. The V

min

boost (

C016

) is detected.

Parameter

Info

C081

Rated motor power

C087

Rated motor speed

C088

Rated motor current

C089

Rated motor frequency

C090

Rated motor voltage

C091

Motor cos ϕ

Note!

Motor parameter identification may be aborted if a special motor (e.g. mid-frequency

motor) is used or if there is a large deviation between inverter and motor power.
Another cause for the abort of the motor parameter identification could be the implau-

sibility of the entered nameplate data, e.g. the entry P = 0 kW for the motor power.