5 enable/inhibit controller, 6 activate/deactivate quick stop, Enable/inhibit controller – Lenze 8400 BaseLine D User Manual
Page 51: Activate/deactivate quick stop, Activate/deactivate quick stop ( 51), 4device control (dctrl)

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05
51
4
Device control (DCTRL)
4.1
Device commands
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.1.5
Enable/Inhibit controller
= "1: : On / start" device command enables the controller, provided that no other sour-
ce of a controller inhibit is active.
The
= "0: Off / ready" device command serves to inhibit the controller, i.e. the power out-
put stages in the controller are inhibited and the speed/current controller of the motor control is re-
set.zurückgesetzt.
• The motor becomes torqueless and coasts down.
• When the controller is inhibited, the status output bCInhActive of the
system
block is set to TRUE.
• When the controller inhibit request is reset, the drive synchronises to the actual speed. For this
purpose,
• If the flying restart circuit is activated in
, the flying restart function parameterised in
is used for the synchronisation to the rotary or standing drive.
Tip!
• The controller can also be enabled or inhibited via the
and
toolbar icons.
•
provides a bit coded representation of all active sources/triggers of a controller in-
hibit.
4.1.6
Activate/Deactivate quick stop
= ""1: On / start" device command activates the quick stop function, i.e. the motor con-
trol is separated from the setpoint selection, and within the deceleration time parameterised in
the motor is brought to a standstill (n
act
= 0).
• A pulse inhibit (CINH) is set if the "Auto-DCB" function has been activated via
.
The
= "0: Off / ready" device command deactivates the quick stop again, provided that no
other source of a quick stop is active.
Tip!
provides a bit coded representation of all active sources/triggers of a quick stop.
Parameter
Info
Lenze setting
Value Unit
Deceleration time - quick stop
2.000 s