background image

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

175

9

Parameter reference

9.2

Parameter list | C00011

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00011

C00012

C00013

C00015

Parameter | Name:

C00011 | Appl.: Reference speed

Data type: UNSIGNED_16

Index: 24564

d

= 5FF4

h

Setting the reference speed

• In the controller, all speed-related signals are processed to one reference variable in percent.

• Set a reference speed here that corresponds to 100 %.

• The frequency of the set reference speed is displayed in

C00059

.

Note:

This is not a maximum limitation!

All values in percent in the controller may be in the range of 0 ... 199.99 %.
Setting range

(min. value | unit | max. value)

Lenze setting

50

rpm

9999 1500 rpm

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00012 | Acceleration time main setpoint

Data type: UNSIGNED_32

Index: 24563

d

= 5FF3

h

FB

L_NSet_1

: Acceleration time of the ramp generator for the main speed setpoint

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

s

999.9 2.0 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00013 | Deceleration time main setpoint

Data type: UNSIGNED_32

Index: 24562

d

= 5FF2

h

FB

L_NSet_1

: Deceleration time of the ramp generator for the main speed setpoint

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

s

999.9 2.0 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00015 | VFC: V/f base frequency

Data type: UNSIGNED_16

Index: 24560

d

= 5FF0

h

V/f base frequency for V/f characteristic control (

VFCplus

)

• The motor voltage increases linearly with the frequency until the base frequency is reached. From this value on,

the motor voltage remains constant, the speed increases and the maximum torque decreases.

• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered auto-

matically. An automatic detection via the motor parameter identification is possible as well.

Setting range

(min. value | unit | max. value)

Lenze setting

7.5

Hz

999.9 50.0 Hz

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10