C00011 | appl.: reference speed, C00012 | acceleration time main setpoint, C00013 | deceleration time main setpoint – Lenze 8400 BaseLine D User Manual
Page 175: C00015 | vfc: v/f base frequency, C012, C011, C013, C015, Apting the v/f base frequency, Is set to
Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05
175
9
Parameter reference
9.2
Parameter list | C00011
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00011
C00012
C00013
C00015
Parameter | Name:
C00011 | Appl.: Reference speed
Data type: UNSIGNED_16
Index: 24564
d
= 5FF4
h
Setting the reference speed
• In the controller, all speed-related signals are processed to one reference variable in percent.
• Set a reference speed here that corresponds to 100 %.
• The frequency of the set reference speed is displayed in
.
Note:
This is not a maximum limitation!
All values in percent in the controller may be in the range of 0 ... 199.99 %.
Setting range
(min. value | unit | max. value)
Lenze setting
50
rpm
9999 1500 rpm
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00012 | Acceleration time main setpoint
Data type: UNSIGNED_32
Index: 24563
d
= 5FF3
h
FB
: Acceleration time of the ramp generator for the main speed setpoint
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
s
999.9 2.0 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000
Parameter | Name:
C00013 | Deceleration time main setpoint
Data type: UNSIGNED_32
Index: 24562
d
= 5FF2
h
FB
: Deceleration time of the ramp generator for the main speed setpoint
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
s
999.9 2.0 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000
Parameter | Name:
C00015 | VFC: V/f base frequency
Data type: UNSIGNED_16
Index: 24560
d
= 5FF0
h
V/f base frequency for V/f characteristic control (
)
• The motor voltage increases linearly with the frequency until the base frequency is reached. From this value on,
the motor voltage remains constant, the speed increases and the maximum torque decreases.
• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered auto-
matically. An automatic detection via the motor parameter identification is possible as well.
Setting range
(min. value | unit | max. value)
Lenze setting
7.5
Hz
999.9 50.0 Hz
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10