Parameter reference
9.2
Parameter list | C00026
178
Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00026
C00027
C00028
C00029
Parameter | Name:
C00026 | AINx: Offset
Data type: INTEGER_16
Index: 24549
d
= 5FE5
h
Offset for analog input
Setting range
(min. value | unit | max. value)
-199.9
%
199.9
Subcodes
Lenze setting
Info
C00026/1
0.0 %
AIN1: Offset
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00027 | AINx: Gain
Data type: INTEGER_32
Index: 24548
d
= 5FE4
h
Gain for analog input
Setting range
(min. value | unit | max. value)
-199.9
%
199.9
Subcodes
Lenze setting
Info
C00027/1
100.0 %
AIN1: Gain
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00028 | AINx: Input voltage
Data type: INTEGER_16
Index: 24547
d
= 5FE3
h
Display of the input voltage at the analog input
Display range
(min. value | unit | max. value)
-10.0
V
10.0
Subcodes
Info
C00028/1
AIN1: Input voltage
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00029 | AINx: Input current
Data type: INTEGER_16
Index: 24546
d
= 5FE2
h
Display of the input current at the analog input
• When the analog input has been configured for current measurement (
= 1 or 2).
is set = 2 (4 ... 20 mA), 0 ... 16 mA is displayed.
Display range
(min. value | unit | max. value)
0.0
mA
20.0
Subcodes
Info
C00029/1
AIN1: Input current
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100