C00600

C00601

C00604

C00606

Parameter | Name:

C00600 | Resp. to DC bus undervoltage

Data type: UNSIGNED_8

Index: 23975

d

= 5DA7

h

Configuration of monitoring of the motor control (group 3)
Selection list

1 Fault
2 Trouble

Subcodes

Lenze setting

Info

C00600/1

2: Trouble

Response to undervoltage in the DC bus

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00601 | Del. resp.to fault: DC bus overvoltage

Data type: UNSIGNED_16

Index: 23974

d

= 5DA6

h

Delay times for error responses
Setting range

(min. value | unit | max. value)

0.00

s

65.00

Subcodes

Lenze setting

Info

C00601/1

2.00 s

Delay time for error activation "DC-bus overvoltage"

• In case of DC-bus overvoltage, an error is only trans-

mitted after this delay time has elapsed.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00604 | Resp. to device overload (Ixt)

Data type: UNSIGNED_8

Index: 23971

d

= 5DA3

h

Response if the adjustable device utilisation threshold (

C00123

) is reached.

• The current device utilisation is displayed in

C00064

.

Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
4 WarningLocked

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00606 | Resp. to motor overload (I²xt)

Data type: UNSIGNED_8

Index: 23969

d

= 5DA1

h

Response if the adjustable motor overload threshold (

C00120

) is reached.

• The current thermal motor load is displayed in

C00066

.

Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
4 WarningLocked

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1