C00033 | ainx: output value, C00034 | ainx: configuration, C00036 | dcb: current – Lenze 8400 BaseLine D User Manual
Page 179: C036, C034/1, C033/1, When, C00034/1, 9parameter reference
Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05
179
9
Parameter reference
9.2
Parameter list | C00033
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00033
C00034
C00036
Parameter | Name:
C00033 | AINx: Output value
Data type: INTEGER_16
Index: 24542
d
= 5FDE
h
Display of the output value in percent of the analog input amplifier
• 100 % ≡ 16384 ≡ +10 V / +20 mA
Display range
(min. value | unit | max. value)
-199.9
%
199.9
Subcodes
Info
C00033/1
AIN1: Output value
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00034 | AINx: Configuration
Data type: UNSIGNED_8
Index: 24541
d
= 5FDD
h
Configuration of the analog input for current or voltage measurement
Selection list
Info
0 0...+10 V
Input signal is voltage signal 0 V ... +10 V
• 0 V ... +10 V ≡ 0 % ... +100 %
1 0...+5V
With external load resistor (250 Ohms):
Input signal is the current signal 0 mA ... 20 mA
• 0 mA ... 20 mA ≡ 0 % ... +100 %
2 1...+5V (4...20mA)
With external load resistor (250 Ohms):
Input signal is the current signal 4 mA ... 20 mA
• 4 mA ... 20 mA ≡ 0 % ... +100 %
• The current loop is monitored for open circuit
(I < 4 mA) by the device.
Subcodes
Lenze setting
Info
C00034/1
0: 0...+10 V
AIN1: Config.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00036 | DCB: Current
Data type: INTEGER_16
Index: 24539
d
= 5FDB
h
Current value in [%] for DC-injection braking
• 100 % ≡ Imax in motor mode (
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
%
150.0 50.0 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100