C00016
C00018
C00019
Parameter | Name:
C00016 | VFC: Vmin boost
Data type: UNSIGNED_16
Index: 24559
d
= 5FEF
h
Boost of the V/f voltage characteristic within the range of low speed or frequency values for the (
) V/f cha-
racteristic control.
• This may increase the starting torque.
• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered auto-
matically. An automatic detection via the motor parameter identification is possible as well.
:
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
%
100.0 0.0 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00018 | Switching frequency
Data type: UNSIGNED_8
Index: 24557
d
= 5FED
h
Selection of the pulse width modulated switching frequency transferred from the inverter to the motor
• When a variable switching frequency is selected, the switching frequency may change as a function of the load
and rotational frequency.
Selection of the switching frequency
Selection list
(Lenze setting printed in bold)
1 4 kHz var./drive-optimised
2 8 kHz var./drive-optimised
3 16 kHz var./drive-optimised
5 2 kHz constant/drive-optimised
6 4 kHz constant/drive-optimised
7 8 kHz constant/drive-optimised
8 16 kHz constant/drive-optimised
21 8 kHz var/4 kHz min.
22 16 kHz var/4 kHz min.
23 16 kHz var/8 kHz min
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00019 | Auto DCB: Threshold
Data type: UNSIGNED_16
Index: 24556
d
= 5FEC
h
Setpoint speed threshold for automatic DC injection braking
• For speed setpoints with values below the thresholds a DC current is injected or the motor is not supplied with
current, depending on the setting.
Setting range
(min. value | unit | max. value)
Lenze setting
0
rpm
9999 3 rpm
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1