Xx.0144.00001, Xx.0144.00002, Xx.0144.00003 – Lenze 8400 BaseLine D User Manual
Page 160: Xx.0144.00004, Xx.0144.00031, 8diagnostics & error management

8
Diagnostics & error management
8.7
Error messages of the operating system
160
Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PS01: No memory module [xx.0144.00001]
PS02: Par. set invalid [xx.0144.00002]
PS03: Par. set device invalid [xx.0144.00003]
PS04: Par. set device incompatible [xx.0144.00004]
PS31: Ident. error [xx.0144.00031]
Response (Lenze setting printed in bold)
None Fault Trouble WarningLocked
Cause
Remedy
Memory module is either not available or not snapped
into place correctly.
• If a memory module has been provided: Plug the me-
mory module into the slot of the standard device in-
tended for this purpose.
• If a memory module has been provided: Check if the
memory module has been plugged-in correctly.
Response (Lenze setting printed in bold)
None Fault Trouble WarningLocked
Cause
Remedy
The parameter set saved to the memory module is inva-
lid because it has not been saved completely.
• This can be due to voltage failure or caused by remo-
ving the memory module while saving the parameter
set.
Ensure voltage supply during the storage process and
that the module remains plugged into the slot.
Response (Lenze setting printed in bold)
None Fault Trouble WarningLocked
Cause
Remedy
The parameter set in the device is invalid.
Consultation with Lenze required.
Response (Lenze setting printed in bold)
No Reaction Fault Trouble Warning
Cause
Remedy
The parameter set saved to the memory module is in-
compatible to the standard device.
• An incompatibility of the parameter set is caused e.g.
when the memory module of an 8400 StateLine is
plugged into an 8400 BaseLine or the parameter set in
the memory module has a higher version than expec-
ted by the standard device.
When the memory modules are exchanged, observe the
downward compatibility:
• OK: BaseLine V2.0 to BaseLine V3.0
• Not OK: StateLine Vx.x to BaseLine Vx.x
• Not OK: BaseLine V3.0 to BaseLine < V3.0
Response (Lenze setting printed in bold)
None Fault Trouble WarningLocked
Cause
Remedy
Incompatible or unknown HW components have been
found.
• Check which HW components are faulty (
duct type code).
• Check temperature range of the device at the start.
• Check whether a software update at Lenze is possible.