C00087 | rated motor speed, C00088 | rated motor current, C00089 | rated motor frequency – Lenze 8400 BaseLine D User Manual
Page 184: C00090 | rated motor voltage, C088, C089, C090, C087, Acco, C00089

9
Parameter reference
9.2
Parameter list | C00087
184
Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00087
C00088
C00089
C00090
Parameter | Name:
C00087 | Rated motor speed
Data type: UNSIGNED_16
Index: 24488
d
= 5FA8
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Note:
It is mandatory to give the rated motor speed for the sensorless vector control (
Setting range
(min. value | unit | max. value)
Lenze setting
50
rpm
9999 1460 rpm
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00088 | Rated motor current
Data type: UNSIGNED_16
Index: 24487
d
= 5FA7
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
A
99.00 21.00 A
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00089 | Rated motor frequency
Data type: UNSIGNED_16
Index: 24486
d
= 5FA6
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Note:
It is mandatory to give the rated motor frequency for the sensorless vector control (
).
Setting range
(min. value | unit | max. value)
Lenze setting
10
Hz
1000 50 Hz
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00090 | Rated motor voltage
Data type: UNSIGNED_16
Index: 24485
d
= 5FA5
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Setting range
(min. value | unit | max. value)
Lenze setting
0
V
1000 400 V
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1