beautypg.com

10 function library – Lenze 8400 BaseLine D User Manual

Page 247

background image

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

247

10

Function library

10.11

LS_DriveInterface

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Inputs

Identifier

DIS code | data type

Information/possible settings

bCInh

C833/14

| BOOL

Enable/Inhibit controller

FALSE Enable controller: The controller switches to the "

OperationEnabled

"

device state, if no other source of a controller inhibit is active.

C158

provides a bit coded representation of all active sour-

ces/triggers of a controller inhibit.

TRUE Inhibit controller (controller inhibit): The controller switches to the

"

SwitchedON

" device state.

bFailReset

C833/15

| BOOL

Reset of error message

In the Lenze setting this input is connected to the digital input controller enable so

that a possibly existing error message is reset together with the controller enable (if

the cause for the fault is eliminated).

TRUE The current fault is reset, if the cause for the fault is eliminated.

• If the fault still exists, the error status remains unchanged.

bStatus_Bit0

bStatus_Bit2

bStatus_Bit3

bStatus_Bit4

bStatus_Bit5

bStatus_Bit14

bStatus_Bit15

C833/16 ... 22

| BOOL

Freely assignable bits in the status word of the controller.

Pre-assignment in the Lenze setting:

Bit0 - (Not connected)
Bit2 Current setpoint in the limitation
Bit3 Speed setpoint reached
Bit4 Actual speed value has reached the setpoint within one hysteresis

band

Bit5 Speed setpoint < comparison value (

C024

)

Bit14 Current direction of rotation:

0 ≡ Clockwise rotation (Cw)

1 ≡ Counter-clockwise rotation (Ccw)

Bit15 Drive is ready for operation