N o t e – ETC Unison Paradigm ACP Configuration Manual v2.1.2 User Manual
Page 96
91
Paradigm Architectural Control Processor Configuration Manual
Off Mode
Property
Units
Default 120V
Default 230V
Default 277V
Curve
not applicable Linear
Linear
Linear
Voltage Regulation
On / Off
Off
Off
Off
Dynamic Preheat
Seconds / Off
Off
Off
Off
Min Scale
Volts
0
0
0
Max Scale
Volts
120V
240V
277V
Transformer Mode
On / Off
Off
Off
Off
Threshold
Control
0
0
0
Reverse Phase Mode
Property
Units
Default 120V
Default 230V
Default 277V
Curve
not applicable Linear
Linear
Linear
Voltage Regulation
On / Off
Off
Off
Off
Dynamic Preheat
Seconds / Off
Off
Off
Off
Min Scale
Volts
20V
30V
40V
Max Scale
Volts
118V
230V
277V
Transformer Mode
On / Off
On
On
On
Threshold
% Control
0
0
0
N o t e :
“Reverse Phase Mode” is selectable only when the module type is the ELV10,
AELV5, or HELV5 electronic low voltage module.
LED Smoothing Reverse
Property
Units
Default 120V
Default 230V
Default 277V
Curve
NA
Linear
Linear
Linear
Voltage Regulation
On / Off
Off
Off
Off
Dynamic Preheat
Seconds/Off
Off
Off
Off
Min Scale
Volts
20V
30V
40V
Max Scale
Volts
118V
230V
277V
Transformer Mode
On/Off
On
On
On
Threshold
% Control
0
0
0
LED Smoothing Forward
Property
Units
Default 120V
Default 230V
Default 277V
Curve
NA
Linear
Linear
Linear
Voltage Regulation
On / Off
Off
Off
Off
Dynamic Preheat
Seconds / Off
Off
Off
Off
Min Scale
Volts
20V
30V
40V
Max Scale
Volts
118V
230V
277V
Transformer Mode
On/Off
On
On
On
Threshold
% Control
0
0
0