Load shedding, Input type / active when – ETC Unison Paradigm ACP Configuration Manual v2.1.2 User Manual

Page 43

background image

3

Programming

38

Load Shedding

Load circuits not set for emergency can either be turned off (via load shedding “On” setting)

or the DRd dimming engine can continue to allow control levels for the circuits that are

excluded from emergency (via load shedding “Off” setting).
Step 7:

Within the Emergency Setup menu, use the touch wheel to scroll to “Load
Shedding” and press enter (

).

Step 8:

Use the touch wheel to change the value for load shedding to “On” or “Off. By

default load shedding is set to “On” and all load circuits not in emergency will turn

off when the contact input is active.

Step 9:

Press enter (

) to accept the selection.

Input Type / Active When

Step 10: Within the Emergency Setup menu, use the touch wheel to scroll to “Input Type”

and press enter (

). The “Input Type” menu displays.

Step 11: Use the touch wheel to select either “Momentary” or “Maintained”. Press enter

(

) to accept the selection.

Step 12: Use the touch wheel to scroll to “Active When” and press enter (

). The “Active

When” menu displays.

Step 13: Use the touch wheel to select either “Open” or “Closed”. Press enter (

) to

accept the selection.

Emergency Setup

Emergency Dimmers

Emergency Level:

100

Load Shedding:

On

Input Type:

Maintained

Active when:

Closed

When the DRd enclosure senses the loss of normal power, it

bypasses the Paradigm ACP and drives selected emergency

load circuits to the emergency level.

Emergency Setup

Emergency Dimmers

Emergency Level:

100

Load Shedding:

On

Input Type:

Maintained

Active when:

Closed

The emergency contact input supports a “Maintained” or

“Momentary” input configured for “Active When Open” or

“Active When Closed”. The default input configuration is a

maintained input, active when closed.