Paradigm Architectural Control Processor Configuration Manual

Step 4:

To maintain individual dimmer settings, press (

) again. To change the ending

number and select a range of dimmers, use the touch wheel or the alpha-numeric

button pad to change the ending number.

Step 5:

Press enter (

) to change focus back to “From dimmer”.

Module Type

:

Step 1:

Use the touch wheel to scroll down to “Module Type” and press enter (

). The

“Module Type” menu will display all possible dimmer module types available for

the rack and voltage selection.

Step 2:

Scroll down the module list and press enter (

) to select a module type.

Changing a module type defaults all dimmer properties for the specified

dimmer(s). Reference

“Dimmer Module Defaults”

on

page 86

for a listing of all

dimmer properties and their defaults.

Step 3:

You can change dimmer properties from their default by using the touch wheel
to scroll down to “Mode” and press enter (

). A full list of dimmer modes will

display.

Changing the dimmer firing mode automatically changes the default settings

for curve, threshold, voltage regulation, minimum voltage and maximum

voltage.

See “Dimmer Properties” on page 92.

Step 4:

Scroll the list and press enter (

) to select a new mode. Reference

“Dimmer

Modes”

on

page 89

for a complete listing of the available modes and their

defaults.

N o t e :

When specifying a range of dimmers, those properties that are not equal among

the selected dimmers will display as empty property fields. Any edits made to the

empty property fields are applied to the entire selected range of dimmers.

Specifying a different module type defaults all dimmer properties for the selected

range.

N o t e :

Changing the module type field to dimmers that do not have dual dimmers (e.g.

fluorescent, constant circuit, and air flow modules) do not display values for

properties or allow edits to dimmer properties.

N o t e :

Module types available for selection are dependent on the rack input voltage,

either 120 VAC, 230 and 240 VAC, or 277 VAC. Reference

“Compatible Loads”,

page 87

.

Module Type

AFM

CC15
CC20
D15
D15E
D15F
D20

D20E
D20F
ELV10
L10
L10F
R15
R20

Module Type

This graphic represents

the 120 VAC module list.

Dimmer Setup

From dimmer:

1 to: 3

Module Type:

D20

Curve:

Mod

Sq

Threshold: 0%
Voltage Reg:

On

Max

Scale:

118V

Mode:

Normal

Each module type has a default set of properties such as the

firing mode, dimmer curve, etc. When changing a module

type, all dimmer properties for the specified dimmer(s) also

change to match the new module type property defaults. You