beautypg.com

ETC Echo Inspire Station User Manual

Overview, Unison, Echo inspire station

background image

E T C I n s t a l l a t i o n G u i d e

Unison

®

Echo Inspire Station

Corporate Headquarters

3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA

Tel +608 831 4116

Fax +608 836 1736

London, UK

Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK

Tel +44 (0)20 8896 1000

Fax +44 (0)20 8896 2000

Rome, IT

Via Pieve Torina, 48, 00156 Rome, Italy

Tel +39 (06) 32 111 683

Fax +44 (0)20 8752 8486

Holzkirchen, DE

Ohmstrasse 3, 83607 Holzkirchen, Germany

Tel +49 (80 24) 47 00-0

Fax +49 (80 24) 47 00-3 00

Hong Kong

Rm 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong

Tel +852 2799 1220

Service: (Americas)

[email protected]

(UK)

[email protected]

(DE)

[email protected]

(Asia)

[email protected]

Web:

www.etcconnect.com

Copyright © 2014 ETC. All Rights Reserved.  Product information and specifications subject to change.

7186M2140  Rev B  Released 2014-08  ETC intends this document to be provided in its entirety.

Overview

Echo™ Inspire stations provide preset, zone, and space combine controls for
use with Unison Echo control systems. Stations are available in 1, 2, 4, 6, and
8 button assemblies, and a 4 button 1 fader station.

Station buttons are backlit by both blue and amber LEDs. The 4 button station
fader knob is backlit with a blue LED.

Prepare for Installation

Inspire stations ship with station electronics, a decorator style wall plate,
termination kit, and a template of standard button labels. The station may be
installed into an industry standard back box (provided by others) or surface
mounted back box (sold separately and available from ETC).

Inspire stations connect to the EchoConnect station communication bus.
EchoConnect is a bidirectional protocol that uses one pair of wires (data+ and
data-) for both data and power. ETC recommends using Belden 8471 (or
approved equal) Class II wire. The total combined length of an EchoConnect
wire run (using Belden 8471, or equal) may not exceed 1,640 feet (500m).

Environmental

Indoor installation - 0-50deg C, 5-95% non-condensing humidity

N o t e :

All control wiring should be installed and terminated by a qualified

installer and should follow standard wiring installation practices.

Leave approximately 10 inches (254mm) of wiring in the back box

for connection and to allow slack for future service needs.

N o t e :

ETC requires that all stations be grounded. Pull an additional 14

AWG (1.5mm

2

) wire for grounding when control wires are not

installed in grounded metal conduit.