beautypg.com

Data loss and power on, Dmx loss behavior and acn loss behavior, Power on behavior – ETC Unison Paradigm ACP Configuration Manual v2.1.2 User Manual

Page 52

background image

47

Paradigm Architectural Control Processor Configuration Manual

Data Loss and Power On

DMX Loss Behavior and ACN Loss Behavior

DMX Loss Behavior and ACN Loss Behavior may be set to “Hold Last Look” or “Wait and

Fade”. Each behavior type is set to “Hold Last Look” by default.

Hold Last Look - holds any active dimmers at whatever levels they were receiving prior
to the loss of data. The last levels are retained until data is restored or the Paradigm
ACP is reset.

Wait and Fade - holds the last levels received when the data was lost for a user-defined
amount of time and then fades those input levels to zero intensity using a user-defined
fade time. The default wait time setting is three minutes and zero seconds. The default
fade time setting is zero minutes and three seconds. Wait and fade times can range
from zero minutes and zero seconds to 60 minutes and zero seconds.

Step 1:

Use the touch wheel to scroll to “Data Loss & Power On” from within the “Arch
Setup” menu and press enter (

). The DMX Loss Behavior, ACN Loss

Behavior, and Power On Behavior menu lists display. Notice the three settings

are separated vertically on the screen. You cannot select the heading, only the

“Mode” and options from within.

Step 2:

Use the touch wheel to scroll to DMX Loss Behavior “Mode:” and press enter
(

) repeatedly to cycle through the options.

Step 3:

When the desired value is displayed, and depending on the value selection,

additional setting options may display. Use the touch wheel to scroll to the next
setting option, if there is one, and press enter (

) or press back ( ) to return

to the “Arch Setup” menu.

When “Wait and Fade” is the mode selection:
a: “Wait Time” and “Fade Time” displays for additional settings. Use the touch

wheel to scroll to “Wait Time” and press enter (

). The focus changes to

the minutes field.

b: Use the touch wheel or alpha-numeric button pad to select the desired

“minutes” value and press enter (

) to change the focus to the seconds

field.

c: Use the touch wheel or alpha-numeric button pad to select the desired

“seconds” value and press enter (

) to accept the new values.

d: Repeat for “Fade Time”.

Step 4:

Repeat for ACN Loss Behavior.

Power On Behavior

Power On Behavior may be set to “None”, or configured to execute an action, such as

playing a preset.

Step 1:

Use the touch wheel to scroll to “Data Loss & Power On” from within the “Arch
Setup” menu and press enter (

). The DMX Loss Behavior, ACN Loss

Behavior, and Power On Behavior menu lists display. Notice the three settings

are separated vertically on the screen. You cannot select the heading, only the

“Mode” and options from within.

DMX Loss Behaviour

Mode:

Hold Last Look

Wait Time: Forever

ACN Loss Behavior

Mode:

Wait and Fade

Wait Time:

3 min 0 sec

Fade Time:

0 min 3 sec

Power On Behavior

Action:

None

Both DMX loss behavior, sACN loss behavior, and

power on behavior have default settings which can

be customized to fit your installation. DMX behavior

settings apply to all DMX input ports. These settings

are contained within the architectural configuration

and may be configured using LightDesigner.