Dimming control menu, Set levels, N o t e – ETC Unison Paradigm ACP Configuration Manual v2.1.2 User Manual
Page 54
![background image](/manuals/559211/54/background.png)
49
Paradigm Architectural Control Processor Configuration Manual
Dimming Control Menu
Set Levels
Step 1:
Use the touch wheel to scroll to “Set Levels” from within the “Dimming Control”
menu and press enter (
). The Set Levels menu list will display.
Step 2:
Use the touch wheel to scroll through the list to select a specific dimmer or use
the alpha-numeric button pad and the “and/thru” functions to select specific or a
range of dimmers. Press enter (
) to accept the selection. The focus changes
to the level value field.
Step 3:
Use the touch wheel to scroll, or the alpha-numeric button pad, to enter a specific
level value for the selected dimmers. This value can be between zero
(displayed as --) and 100% (displayed as FL). Press enter (
) to accept the
selection.
Step 4:
When all dimmers are set to the desired level, press back ( ) to return to the
“Dimming Control” menu.
Step 5:
When you exit the “Set Levels” menu, you will be prompted for confirmation if you
would like to “Release Set Levels”. Selecting “Yes” returns all set levels to the
default value. Selecting “No” causes all set levels to remain until released.
N o t e :
“NA” indicates a dimmer that cannot be set to a level such as a CC20.
N o t e :
Dimmers that are controlled from the “Set Levels” action cannot be controlled from
the architectural system, DMX, or sACN until they have been released.
Dimming Control
1 Set Levels
2 Dimmer Check
3 Release Set Levels
The “Dimming Control” menu is selectable only when the
Paradigm ACP is installed in a host DRd enclosure.
The “Dimming Control” menu is provided to set dimmer levels,
check dimmers and release any set dimmer levels. Direct
access to the “Dimming Control” menu is also selectable from
the Control Menu Shortcut (
) button.
Set Levels
1
55 2 -- 3 FL
4 -- 5 50 6 --
7 50 8 FL 9 --
10 50
11 25
12 FL
13 NA
14 NA
15 FL
16 --
17 FL
18 75
19 --
20 50
21 50
All configured dimmers are displayed in the “Set Levels” menu
list. You may use “and / thru” functions to specify a selection or
range of dimmers for level setting.
1 and 5 thru 12
1
55
2 -- 3 FL
4 -- 5
55
6
55
7
55
8
55
9
55
10
55
11
55
12
55
13 NA
14 NA
15 FL
16 --
17 FL
18 75
19 --
20 50
21 50
Setting a level value when multiple dimmers are
selected will set all selected dimmers to that level
value. Once your dimmer selection is made, press
enter (
) to accept the selection. The focus changes
to the level value setting. To remove the last selected
dimmer from the selection, press the back button
( ). Continue pressing the back button ( ) to clear
all undesired dimmers from the selection.