Paradigm Architectural Control Processor Configuration Manual

Install the Paradigm ACP

The Paradigm Architectural Control Processor (P-ACP) is designed to slide in the bottom

module slot of a Unison DRd or an ERn enclosure. All data terminations used with the

Paradigm ACP are terminated to the right and left I/O boards in the related enclosure. Install

the Paradigm ACP only after the enclosure has been installed and all wires have been

terminated properly.

Step 1:

Open the enclosure door.

Step 2:

Rest the Paradigm ACP on the bottom lip of the enclosure, aligning both left and

right edges with the module slots.

Step 3:

Slide the Paradigm ACP into the rack.

Step 4:

Press gently on each corner of the Paradigm ACP to ensure proper connection

with the card edge connectors on the left and right I/O boards. When power is

applied, the status LEDs will illuminate and the ACP will load the operating

software.

Set Processor Identity and IP Address

Prepare your Paradigm ACP to receive a LightDesigner configuration file. The procedure

to set processor identity and IP address is determined by the type of system you are

installing, either a single or a multiple processor system.

W A R N I N G :

Rack enclosures installed without an accessible power disconnect device

cannot be serviced or operated safely. Follow all local codes and

restrictions. Before removing dimmer or control modules for service, de-

energize main feed to the rack and follow appropriate Lockout/Tagout

procedures as described in NFPA Standard 70E. It is important to note that

electrical equipment such as dimmer racks can present an arc flash safety

hazard if improperly serviced. This is due to available large Short Circuit

Currents on the feeders of the equipment. Any work on energized

equipment must comply with OSHA Electrical Safe Working Practices.

N o t e :

DRd and ERn enclosures are shipped standard with a module retention bar which

secures all modules into the enclosure, requiring a tool for module removal.
Before installing the Paradigm ACP module or any other modules, be sure to

release the retention bar first, install the modules, then replace and secure the

retention bar.