3
Programming
42
Connect a Device
Step 1:
Scroll to “Connect a Device” and press enter (
). Depending on the filter criteria,
the list of unconnected stations are shown, listed by the station name as provided
by the configuration.
Step 2:
Scroll to select the desired station for connection (binding) and press enter (
).
The “Connect to:” menu lists all unconnected neuron IDs, of matching type, that
are discovered for connection.
Step 3:
Scroll to select the desired neuron ID from the list and press the control menu
shortcut
button to send a wink command for the selected device. A wink
commands the physical Lon device to blink its LEDs for identification.
Disconnect a Device
Step 1:
Scroll to “Disconnect a Device” and press enter (
). Depending on the filter
criteria, if any, the list of connected devices displays with the station name
provided by the configuration.
Step 2:
Scroll to select the desired station and press enter (
). The selected station is
will no longer be bound to the processor and will be displayed in the “Connect a
Device” list.
Wireless HF Channel
All wireless devices must be on the same HF Channel to communicate on the lighting
control network. By default this setting is HF Channel 10. To configure the HF Channel
property for a Handheld Touchscreen, reference the Paradigm Handheld Touchscreen and
Wireless Accessories Configuration and User Manual. To configure the HF Channel for a
Docking Station or Wireless Access Station, first connect the device using the
menu.
Step 1:
Scroll to “Wireless HF Channel” and press enter (
). Depending on the filter
criteria, the list of unconnected wireless stations are shown, listed by the station
name as provided by the configuration.
Step 2:
Scroll to select the desired wireless station, or select “All Devices in List” for HF
Channel configuration and press (
). The HF Channel selection screen
displays.
Step 3:
Scroll to select the station and press (
). The current HF Channel setting is in
focus.
Step 4:
Use the numeric keypad or the scroll wheel to select the new HF Channel setting
and press enter (
) to set.
N o t e :
Pushing a button on a Unison Heritage station or issuing a device’s service pin will
automatically highlight its neuron ID in the “Connect to:” list if the station type
matches the previously selected station type.