Paradigm Repeater Module Installation

Paradigm Repeater Module Setup Guide

Page 1 of 4

Electronic Theatre Controls, Inc.

Corporate Headquarters

„

3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA

„

Tel +608 831 4116

„

Fax +608 836 1736

London, UK

„

Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK

„

Tel +44 (0)20 8896 1000

„

Fax +44 (0)20 8896 2000

Rome, IT

„

Via Ennio Quirino Visconti, 11, 00193 Rome, Italy

„

Tel +39 (06) 32 111 683

„

Fax +44 (0) 20 8752 8486

Holzkirchen, DE

„

Ohmstrasse 3, 83607 Holzkirchen, Germany

„

Tel +49 (80 24) 47 00-0

„

Fax +49 (80 24) 47 00-3 00

Hong Kong

„

Rm 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong

„

Tel +852 2799 1220

„

Fax +852 2799 9325

Service: (Americas)

[email protected]

„

(UK)

[email protected]

„

(DE)

[email protected]

„

(Asia)

[email protected]

Web:

www.etcconnect.com

„

QSF 4.1.9.1

„

Copyright © 2008 ETC. All Rights Reserved.

„

Product information and specifications subject to change.

7182M2210

„

Rev A

„

Released 08/2008

The Paradigm station repeater (P-REP) module extends the system station bus length by 1,640
feet (500m) and adds support for up to 30 additional stations.

The Paradigm dual station repeater (P-DREP) module extends the system station bus length 3,280
feet (1,000m) through two separate Echelon segments, supporting 1,640 feet (500m) of additional
LinkPower station wire each, and adds support for up to 30 additional stations.

Both repeater module types may be utilized in the top module slots of the ERn4 rack enclosure.

The following table lists the recommended control wire types used in a typical Unison installation
and the maximum wire runs allowed.

Purpose

Link Power

(Belden 8471)

DMX

(Belden 9729)

Ethernet

(Cat5 /Belden

1583a)

Feet

Meter

Feet

Meter

Feet

Meter

Total length of control wire
(without repeater module)

1640

500

1600

487

328

100

Maximum wire length (ERn
to station)

1313

400

1600

487

N/A

N/A

Maximum repeater distance

1640

500

N/A N/A

N/A

N/A

Blank module (ERn-BM)

Paradigm station repeater module (P-REP)

Paradigm architectural control processor (P-ACP)

Paradigm station power module (P-SPM)

Paradigm dual station repeater module (P-DREP)

Paradigm station power module (P-SPM)