beautypg.com

Patch by dmx start, N o t e – ETC Unison Paradigm ACP Configuration Manual v2.1.2 User Manual

Page 39

background image

3

Programming

34

Patch By DMX Start

Two universes of DMX control are available in the Paradigm Architectural Control

Processor, DMX port A and DMX port B. When the Paradigm ACP is configured to be

installed in a host DRd rack, DMX port B is automatically dedicated, by default, to output

DMX to the host dimmer rack, as well as other external DMX devices. This setting cannot

be changed. DMX port A may be set to either input DMX or output DMX. These settings are

specified in the LightDesigner configuration files, New Project Wizard, or processor

property editor.

A universe is a group of 512 contiguous control channels. When using the “Patch by DMX

Start” menu, addresses may start at one or any number up to 512 minus the number of

dimmers in the enclosure, depending on the type of enclosure(s) you are programming.

Rack limits include:

DRd6= channel 500

DRd12= channel 488

DRd12-48 = channel 464

The highest DMX address for any dimmer allowed is 512.

Dimmers set for dimmer doubled mode or to hi-resolution 16 bit DMX operation from the

Dimmer Setup menu require two channels of control (two DMX addresses).

A dimmer set for dimmer doubled mode is applied a +256 address offset from the
starting address for the second control channel value of that dimmer. For example if
dimmer 1 is set to dimmer doubled mode and DMX address 1, the second channel of
control for dimmer 1 would be DMX address 257, by default.

A dimmer set for hi-resolution 16 bit mode is applied a +1 address offset from the
starting address for the second control channel value of that dimmer. For example if
dimmer 2 is set to hi-resolution 16 bit mode and DMX address 2, the second channel
of control for dimmer 2 would be DMX address 3, by default.

This second control channel will not display in the Patch by DMX Start menu, reference

“Patch Dimmers”

for address details about each dimmer.

Step 1:

Use the touch wheel to scroll or use the alpha-numeric button pad to select the

desired dimmer 1 start address. Notice that the ending dimmer in the rack will

automatically assume a DMX address following the start address. For example

in a DRd6 dimmer rack, if the first dimmer is set to address 115, the ending

dimmer address will be 126, by default.

Step 2:

Press enter (

) to accept the selection. The Dimming Setup Menu will display.

N o t e :

Any change in the default 1 to 1 patch or to an advanced patch creates a warning

dialog for your attention. You must confirm whether or not the existing dimmer

patch should be overwritten by the newly specified dimmer patch.

Patch by DMX Start

Dimmer 1 Start:

111

Dimmer 24 End:

135

Patches all dimmers
sequentially with a
DMX start address.
End is info only.

When patching by DMX start address, all dimmers in the rack

are set to default address values determined by the DMX

address of the first dimmer in the rack.

By default, the dimmers are patched 1 to 1. This means that

dimmer 1 is patched to DMX address 1, dimmer 2 is patched to

DMX address 2, and so on. “---” is displayed when a dimmer is

not patched to a DMX address.