ETC Echo Lockout Station User Manual
Overview, Unison, Echo lockout station
E T C I n s t a l l a t i o n G u i d e
Unison
®
Echo Lockout Station
Corporate Headquarters
3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA
Tel +608 831 4116
Fax +608 836 1736
London, UK
Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK
Tel +44 (0)20 8896 1000
Fax +44 (0)20 8896 2000
Rome, IT
Via Pieve Torina, 48, 00156 Rome, Italy
Tel +39 (06) 32 111 683
Fax +44 (0)20 8752 8486
Holzkirchen, DE
Ohmstrasse 3, 83607 Holzkirchen, Germany
Tel +49 (80 24) 47 00-0
Fax +49 (80 24) 47 00-3 00
Hong Kong
Rm 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong
Tel +852 2799 1220
Service: (Americas)
(UK)
(DE)
(Asia)
Web:
Copyright © 2014 ETC. All Rights Reserved. Product information and specifications subject to change.
7140M2120 Rev A Released 2014-08 ETC intends this document to be provided in its entirety.
Overview
Echo Lockout station enables security for stations within a space, preventing
unwanted control-activation from all stations within the space while the keyed
lockout is enabled.
Prepare for Installation
Echo Lockout stations ship with station electronics, faceplate, termination kit,
(2) keys, and installation hardware. The station may be installed into a standard
back box (provided by others) or surface mounted back box (sold separately
and available from ETC).
Lockout stations connect to the EchoConnect station communication bus.
EchoConnect is a bidirectional protocol that uses one pair of wires (data+ and
data-) for both data and power. ETC recommends using Belden 8471 (or
approved equal) Class II wire. The total combined length of an EchoConnect
wire run may not exceed 1,640 feet (500m).
Environmental
•
Indoor installation - 0-50deg C, 5-95% non-condensing humidity
N o t e :
All control wiring should be installed and terminated by a qualified
installer and should follow standard wiring installation practices.
Leave approximately 10 inches (254mm) of wiring in the back box
for connection and to allow slack for future service needs.
N o t e :
ETC requires that all stations be grounded. Pull an additional
14 AWG (1.5mm
2
) wire for grounding when control wires are not
installed in grounded metal conduit.
The Lockout station is designed for use with any
EchoConnect-enabled system including Echo Zone
Controllers, Echo Relay Panels, Sensor3 and Unison DRd
with Echo ACP.