Overrides, Clear arch output, Overrides clear arch output – ETC Unison Paradigm ACP Configuration Manual v2.1.2 User Manual
Page 60: N o t e
55
Paradigm Architectural Control Processor Configuration Manual
Overrides
Step 1:
Scroll to select “Overrides” from the “Arch Control” menu and press enter (
).
The “Select Overrides” menu list displays all overrides created in the
LightDesigner configuration along with their current status. Override status can
be either “Active” or “Inactive”. Overrides are listed in alphabetical order.
Step 2:
Scroll to select an override and press enter (
). The override status toggles
between “Active” and “Inactive” each time enter (
) is pressed.
Clear Arch Output
Step 1:
Scroll to select “Clear Arch Output” from the “Arch Control” menu and press enter
(
).
Step 2:
Scroll to select option and press enter (
).
•
Select “Cancel” to return to the “Arch Control” menu.
•
Paradigm maintains a cache of levels last sent from DMX called the “Boot
Look”. “Clear Boot Look” only removes those levels from output.
•
“Clear ALL Arch Control” sends all architectural control channels to default
levels (usually zero for zones and home positions for multi-parameter
fixtures). This will also clear the “Boot Look”, however gateway or DMX pass-
through data will remain unaffected.
N o t e :
Channels may have a minimum, or default, attribute level defined that is non-zero.
When “Clear ALL Arch Ctrl” is enabled, the channel will be restored to the defined
default levels.
Daylight:
Inactive
Nite Mode: Inactive
Occupancy:
Active
Timed Event:
Inactive
Select Override
The “Overrides” menu provides the tools to change the current
state of an override. Overrides are created in the LightDesigner
configuration to override timed events from affecting lighting, or
to integrate occupancy or daylight harvesting sensors into a
lighting system.
This will affect
local Arch control
for both DMX and ACN.
Select an option:
Cancel
Clear Boot Look only
Clear ALL Arch Ctrl
Clear Arch Output
The “Clear Arch Output” menu provides the tools to zero only
intensities or reset all attribute levels to zero for all channels
connected to the Paradigm ACP (all local arch control for both
DMX and sACN outputs). This action is similar to a blackout
command from a control console and fade times do not apply.