4. Commissioning
4-22
Festo P.BE-SPC11-SYS-EN en 1406e
Use the buttons as follows to activate the modification mode:
1. Make sure that the drive is standing still.
2. Press all three buttons on the SPC11 at the same time.
The display shows the letter A (Amplification stage) and
the stage set (here 02).
(A.02)
If you have activated the modification mode by mistake, you
can abort the procedure by switching off the power supply. If
you have already carried out the teach procedure, you can in
this way avoid the need to carry out this procedure again.
With the +/- buttons, you can modify the parameter displayed
and transfer it with Enter.
When you change the parameters A, C, S, L or r:
When the last parameter has been transferred, the SPC11
then indicates readiness to carry out the teach procedure
(t flashes).
Create status as at delivery
Condition
The measuring system must not be connected. There must
be a 0-signal at input Remote (I8). The compressed air sup-
ply must be switched off.
Use the buttons as follows to create the status as at delivery:
1. Switch off the compressed air and the power supplies.
2. Disconnect the measuring system cable from the
measuring system.