4. Commissioning
4-10
Festo P.BE-SPC11-SYS-EN en 1406e
4.2.3 Parameter o (options)
With this parameter, you can change the signal behaviour of
the SPC11 and switch off certain standard functions (from
Version 1.41).
Please note
The factory setting (o-parameter = 0) means:
–
No option selected. Standard behaviour active.
Standard behaviour at factory setting (o-parameter = 0):
–
Output O5 supplies Error signal
–
Positioning time monitoring (10 s) active
–
Constant adaptation active
–
Soft end position behaviour active
–
Input I4 can be used for the positioning order to the
taught intermediate position P.04
In the factory setting (o-parameter = 0), the above behaviour
is identical to the previous version (there no options were
selectable).
Internally, the decimal value is interpreted as binary. A spe-
cific option is assigned to each bit (see following table). Only
allowable option combinations can be set. This results in a
possible value range of 00 to 79 for the o-parameter.