4. Commissioning

4-10

Festo P.BE-SPC11-SYS-EN en 1406e

4.2.3 Parameter o (options)

With this parameter, you can change the signal behaviour of
the SPC11 and switch off certain standard functions (from
Version 1.41).

Please note
The factory setting (o-parameter = 0) means:

No option selected. Standard behaviour active.

Standard behaviour at factory setting (o-parameter = 0):

Output O5 supplies Error signal

Positioning time monitoring (10 s) active

Constant adaptation active

Soft end position behaviour active

Input I4 can be used for the positioning order to the
taught intermediate position P.04

In the factory setting (o-parameter = 0), the above behaviour
is identical to the previous version (there no options were
selectable).

Internally, the decimal value is interpreted as binary. A spe-
cific option is assigned to each bit (see following table). Only
allowable option combinations can be set. This results in a
possible value range of 00 to 79 for the o-parameter.