beautypg.com

Festo Контроллер крайних положений SPC11 User Manual

Page 69

background image

4. Commissioning

4-11

Festo P.BE-SPC11-SYS-EN en 1406e

Parameter o (options)

Bit

Decimal
value at 1

Option

Description

0

1

Output O5:
– Ready signal

(instead of Error
signal)

Use O5 for Ready signal – instead of Error signal.
Permits monitoring of operational readiness:
– The output O5 supplies a 1-signal if the SPC11 is ready to

operate.

– A 0-signal at this output indicates that the SPC11 is not

yet ready to operate, or there is a system or positioning
error.

1

2

Switch off
positioning time
monitoring

Switches off the time monitoring during a positioning order.
It is then not monitored whether the position is reached
within approx. 10 s.

2

4

Switch off con-
stant adaptation

Switch off constant adaptation. Adaptation is then active
after operating voltage is switched on only within the first
20 strokes.

1)

3

8

Switch off soft end
position behaviour

Switches off soft end position behaviour. Travelling into the
end position takes place with somewhat more remaining
energy. You can reduce the cycle time with this function
(up to max. 15 %, depending on drive and mass load).

4

16

Parameterise
DNCI/DDPC with L
< 999 mm

From FW 1.81: For long drives DNCI/DDPC: with bit 4 of the
O parameter, 1000 mm is added to the length set with the L
parameter. After switch-off and switch-on or with a new
parameterisation, this is indicated with "L. 1".
As a result, lengths of up to 1999 mm can be set.

1)

With oscillating mass load, constant adaptation can negatively influence travel behaviour.