beautypg.com

1 error messages on the spc11 – Festo Контроллер крайних положений SPC11 User Manual

Page 111

background image

5. Diagnosis and error treatment

5-3

Festo P.BE-SPC11-SYS-EN en 1406e

5.1

Error messages on the SPC11

If a fault occurs, the SPC11 will display a fault number and
react as follows:

The valve slide of the proportional directional control
valve will then be brought into the intermediate position
(flow blocked). The drive is uncontrolled.

Output O5 assumes the defined signal status (dependent
on parameter o, see chapter 4.2.3):

Error signal (factory setting): O5 is set

or

Ready signal: O5 is reset

No new positioning task will be accepted.

To clear the fault (dependent on parameter o, see
chapter 4.2.3):

S

switch the operating voltage off and then on again

or

S

acknowledge the fault with input I6 (see section 5.3).

Fault no.

Operating status

Eliminating faults

Measuring system not connected or
measuring system cable fracture

S

Connect the measuring system or
check the cable

Incorrect direction of movement ascertained
during identification or reference travel;
Tubing is incorrectly connected or an
incorrect measurement system signal

S

Check the tubing of the propor-
tional directional control valve
and correct if necessary

S

With drive type DNCI-...:
Check installation of the sensor
and correct, if necessary