beautypg.com

A.1 the spc11 remote inputs – Festo Контроллер крайних положений SPC11 User Manual

Page 125

background image

A. Start-up via digital inputs/outputs

A-3

Festo P.BE-SPC11-SYS-EN en 1406e

A.1

The SPC11 remote inputs

A 1-signal at the Remote input deactivates the SPC11 buttons.
The button functions can then be called up via the digital
inputs (I5...7). This permits start-up via external operating
buttons or a higher-order PLC/IPC.

Input

Function

Description

I7

{/-

With position change:
A 1-signal (min. 20 ms) at this input continuously reduces the
position value as long as the 1-signal is present (drives moves
toward the measuring system zero point).
With parameter change:
A 1-signal (min. 20 ms) at this input reduces the parameter
value by one.

1)

I6

Enter/Teach
(

> 2 s)

Esc (

< 1 s)

A 1-signal at this input (longer than 2 seconds) confirms the
parameter value or starts the teach procedure.

A short 1-signal (

< 1s ) breaks off the procedure.

I5

+/}

With position change:
A 1-signal (min. 20 ms) at this input continuously increases
the position value as long as the 1-signal is present (drives
moves away from the measuring system zero point).
With parameter change:
A 1-signal (min. 20 ms) at this input increases the parameter
value by one.

1)

1)

Continuous change of parameter values is only possible via the SPC11 buttons.