Parallel Calibration

The parallel calibration function can be used
to offset cables losses.

External Voltage and Resistance Control

Voltage/Resistance controlled remote
control can only be used with the master
unit.

The full scale current (in parallel) is
equivalent to the maximum external voltage
or resistance.

Internal Resistance

For 2 units in parallel, the internal resistance
is actually half of the setting value.

For 3 units in parallel, the internal resistance
is actually a third of the setting value.

For 4 units in parallel, the internal resistance
is actually a fourth of the setting value.

See function setting F-08 for internal
resistance settings, page 101.

Bleeder Control

The Master unit is used to control the
bleeder settings. The bleeder resistors in all
the slave units are always turned off when
in parallel mode.

Output Voltage/
Output Current

Model

1 unit 2 units 3 units 4 units

PSU 6-200

6V

6V

6V

6V

200A

400A 600A

800A

PSU 12.5-120 12.5V 12.5V 12.5V

12.5V

120A

240A 360A

480A

PSU 20-76

20V

20V

20V

20V

76A

152A 228A

304A

PSU 40-38

40V

40V

40V

40V

38A

76A

114A

152A

PSU 60-25

60V

60V

60V

60V

25A

50A

75A

100A