142
Isolated Analog Control Option Overview
Overview
The Isolated Analog Connectors are 8 pin
sockets that are optically isolated from the
power supply, allowing inputs with ground
references that differ to the power supply. The
isolated options include either an isolated
voltage (0~5V/0~10V) interface or an isolated
current (4~20mA) interface. Only one type of
isolated interface can be used at any one time.
The pins used determine what remote control
mode is used.
Note
The GPIB Option (PSU-GPIB), the isolated voltage
option (PSU-ISO-V) and the isolated current
option (PSU-ISO-I) all use the same option slot,
meaning that only one of the three options can be
used at any one time.
Pin Assignment
Isolated Voltage
Connector
8
7
6
5
4
3
2
1
0 - 5V / 0 - 10V
ISOLATED PROGRAMMING
Isolated Current
Connector
8
7
6
5
4
3
2
1
4 - 20mA
ISOLATED PROGRAMMING
Pin name
Pin number
Description
SHIELD
1 Shield, connected internally to the chassis of the
power supply.
+VPROG_ISO
2 Output Voltage programming input.
+IPROG_ISO
3 Output Current programming input.
GND_ISO
4 Ground for programming signals.
GND_ISO
5 Ground for programming signals.
+VMON_ISO
6 Output Voltage monitoring output.
+IMON_ISO
7 Output Current monitoring output.
Shield
8 Shield, connected internally to the chassis of the