Not equal to (ne), C.4.4 not equal to (ne) – Nematron Pointe Controller User Manual
Page 387
Pointe Controller User Guide
Appendix C: Ladder Diagram Block Reference
385
C.4.4 Not Equal to (NE)
When used in a Ladder Diagram, the NE block checks to see if one input is not
equal to another and uses the result — false or true — to set the output rung
state.
Select the
tool (from the
Comparison Blocks
toolbar) and click on a ladder
rung to insert the following block:
Once the block is inserted, you can double-click on it to
configure
it.
Functional Description
When EN becomes on, the block function is executed: the Input Value 1 (IN1) is
compared with the Input Value 2 (IN2) and the result is placed in the Output (Q).
If IN1 is not equal to IN2, then “true is placed in Q. If IN1 is not not equal to IN2,
then “false is placed in Q.
The result placed in Q determines the state of the rung passed to the right: a
“true result turns the rung on and a “false result turns the rung off.
The block function is executed every time the ladder is
scanned
, so long as EN
remains on. If EN becomes off, then Q is immediately turned off regardless of the
values of IN1 and IN2.
Configuration Reference
The parameters of this block are described in the following table:
Param
Name
Config
Var Type
Description
EN
Enable
no
-
The state of the rung (off/on)
received from the left.
Q
Output
no
-
The result — false or true — of
comparing the two input values.
The result becomes the state of the
rung (off/on) passed to the right.