Appendix A: OptiLogic Technical Specifications
Pointe Controller User Guide
270
o
Over 30 KHz – The maximum pulse frequency will be greater
than or equal to 30 KHz.
To configure Frequency Selection, click the
to the right and select a
frequency option from the pop-up menu.
Counter Value – Tag to which the current value of the pulse counter will
be written. Mapped to a 32-bit Signed Input tag (%ID).
To configure Counter Value, click the
to the right and select a tag from
the pop-up menu. Each tag can be used only once.
Frequency – A sample of counted pulses taken over a predetermined
time period. The length of the period depends on the Frequency Selection
(above). If “Up to 30 KHz” is selected, then the period is the most recent 1
second. If “Over 30 KHz” is selected, then the period is the most recent
200 milliseconds (msecs). The total number of pulses counted during that
period is written to the Frequency tag. Mapped to a 16-bit Signed Input
tag (%IW).
To configure Frequency, click the
to the right and select a tag from the
pop-up menu. Each tag can be used only once.
Hold Count – Bit to pause and resume the counter. When the bit
becomes ON, the counter is paused. When the bit becomes OFF, the
counter is resumed from its last value. Mapped to an Output Bit tag
(%QX).
To configure Hold Count, click the
to the right and select a tag from
the pop-up menu. Each tag can be used only once.
Preset Value – Value to which Counter Value will be forced whenever Z
Preset, LS Preset, or Force Preset becomes ON (see below). Mapped to any
32-bit Signed tag (%ID, %MD, or %QD).
To configure Preset Value, click the
to the right and select a tag from
the pop-up menu. Each tag can be used only once.
Z Preset – Option to allow the status of Input Z to force the Preset Value.
o
If Disabled (default), then Input Z can be used as a generic DC
input.
o
If Enabled, then Counter Value will be forced to Preset Value
when Input Z becomes ON.
To configure Z Preset, click the
to the right and select an option
(Disabled or Enabled) from the pop-up menu.
LS Preset – Option to allow the status of Input LS to force the Preset
Value.
o
If Disabled (default), then Input LS can be used as a generic DC
input.