A.7
OL2208 DC Digital Input Module
The OL2208 DC Digital Input module can be used in either
sourcing or sinking application. (All eight inputs must be
used in the same manner.) Each input is optocoupled to
provide system isolation. Individual LED indicators provide
a visual feedback of current status.
Technical Specifications
Card Cage Power Required
60 mA
Input Type
DC Optocoupled
Inputs
8
Status Indicators
Logic Side LED
Voltage Range
10 – 30 VDC
Input Impedence
2.7K ohms
Min. On Current (per point)
3.3 mA
Max. On Current (per point)
11 mA
Commons
2 (connected internally)
Terminal Strip
Plug In (removable)
Terminal Screws
Slotted (0.1” blade max.)
Max. terminal wire gauge
18 AWG (use copper conductors)
Terminal block torque
2.2 lb-in
Required Temp. rating of
field installed conductors
60°C / 75°C
Weight
1.2 oz (34g)
Type
1
Subtype
1