beautypg.com

Types of modbus data, 2 types of modbus data – Nematron Pointe Controller User Manual

Page 222

background image

Chapter 8: Networked Operations

Pointe Controller User Guide

220

8.2.2 Types of Modbus data

PointeControl allows mapping to four different Modbus data types: Coils,
Discretes, Analogs, and Registers. The following table shows which variables in
Logic Memory can be mapped to each data type:

Coils

(00001-

09999)

read/write

Discretes

(10001-

19999)

read only

Analogs

(30001-

39999)

read only

Registers

(40001-

49999)

read/write

Inputs

%IX (Bits)

X

%IUB (8 Bit Unsigned)

X

%IB (8 Bit Signed)

X

%IUW (16 Bit Unsigned)

X

%IW (16 Bit Signed)

X

%IUD (32 Bit Unsigned)

X

%ID (32 Bit Signed)

X

%IF (32 Bit Real)

X

Memory

%MX (Bits)

X

X

X

%MUB (8 Bit Unsigned)

X

X

%MB (8 Bit Signed)

X

X

%MUW (16 Bit Unsigned)

X

X

%MW (16 Bit Signed)

X

X

%MUD (32 Bit Unsigned)

X

X

%MD (32 Bit Signed)

X

X

%MF (32 Bit Real)

X

X

Outputs

%QX (Bits)

X

X

X

%QUB (8 Bit Unsigned)

X

X

%QB (8 Bit Signed)

X

X

%QUW (16 Bit Unsigned)

X

X

%QW (16 Bit Signed)

X

X

%QUD (32 Bit Unsigned)

X

X