Inputs - outputs, Applications – Micromod RetroPAK: SLC Configuration Manual User Manual
Page 392
Command Series Migration to MOD 30ML
Extras – Reject to Manual
INPUTS - OUTPUTS
Signal
Type
Block
Description
S1
Input – S1
Discrete
QUALLOGIC
(EX)
Connect to the QUALLOGIC.S1 signal
of the compound. Averaged Value.
S2
Input – S2
Short State
TRIGGER
(SM)
Connect to the TRIGGER.S2 signal of
the compound.
APPLICATIONS
This compound can be used for an on demand write (on a low to high transition of the S2
input) for any attribute of a function block. This is useful especially if the attribute is not
connectable (for example OPMS, SP of the PID block). The data to be written can be
specified in the SM block’s configuration I the Data Source field as shown in the figure
below or can be connected to the DATAINP attribute of the SM block.
Reject to Manual
SM block
R - 2