Micromod RetroPAK: SLC Configuration Manual User Manual

Page 172

background image

Command Series Migration to MOD 30ML

Pre-Configured – Cascade Control

S18 PID1,

PID2,

PIDFAIL

Input – S18 Count Algorithm Type. Choose the type in the

respective PID block. Open the Control
tab and select the value using the
ALGORITHM TYPE drop-down
menu.

S19 N/A

N/A

N/A

S21 PID1,

PID2,

PIDFAIL

Input – S21
Discreet

Controller Action. Choose the action in
the respective PID block. Open the
General tab and select the desired
CONTROLLER ACTION.

N

AMSTATION

Output – N
Floating Point

Output of the compound.
AMSATION.N is already Connected to
the Input attribute of the built-in output
block AOUT1.

FC21-
S7

PID1HIALM,
PID2HIALM

Input – Hi Alarm
Trip Value
Floating Point

Open the respective Process Alarm
Display block (PAD1HIALM or
PAD2HIALM) and Change the TRIP
VALUE
under the General tab.

FC21-
S8

PID1LOALM,
PID2LOALM

Input – Lo Alarm
Trip Value
Floating Point

Open the respective Process Alarm
Display block (PAD1LOALM or
PAD2LOALM) and Change the TRIP
VALUE
under the General tab.

FC21-
S14

PID1, PID2,
PIDFAIL

Input – Setpoint
Track Input
Floating Point

Open the respective PID block (PID1,
PID2, PIDFAIL)
and check the box
Enable Setpoint tracking and then
connect a signal to the SPTI attribute of
the PID block.

P5- 4